System Testing and Maintenance
65
Liebert
®
Mini-Mate2
™
POT2 controls the amperage at which the drain will energize and is clearly marked in percentages.
This adjustment is factory-set at 85%, which indicates that the unit will drain when the amperage
falls off to 85% of the capacity set point. Raising the value increases the frequency of drain cycles.
Lowering the value decreases the frequency of drain cycles.
The frequency should be increased for highly conductive water and decreased for less conductive
water. If adjustment is necessary and a change of 3 to 4 percent in either direction does not permit
normal operation of the unit, consult your Liebert supplier.
The POT1 controls the duration of the drain cycle. This adjustment is factory-set at 60 seconds and
should not be readjusted without consulting your Liebert supplier.
The DIP switch settings are used to set the capacity of the humidifier. If the humidifier is replaced in
the field, the DIP switches should be set to the required settings described below.
9.3
Replacement Procedures
9.3.1 Compressor Replacement
Infrequently, a fault in the motor insulation may result in a motor burnout (if system is properly
installed, motor burnout rarely occurs). Primarily this type of failure is due to mechanical or
lubrication problems, where the burnout is a secondary consequence.
Early detection can prevent a large percentage of the problems that can cause compressor failures.
Periodic maintenance inspections by alert service personnel (i.e., identification of abnormal
operation) can be a major factor in reducing maintenance costs. It is easier and more cost-effective to
implement the necessary preventative steps that ensure proper system operation; rather than ignore
a problem until it results in compressor failure and costly replacement. When troubleshooting a
compressor problem, check all electrical components for proper operation:
• Check all fuses and circuit breakers.
• Check pressure switch operation.
• If a compressor failure has occurred, determine whether its cause is an electrical or mechanical
problem.
Mechanical Failure
: If a mechanical failure has occurred, the compressor must be replaced. If a
burnout occurs, correct the problem and clean the system. It is important to note that successive
burnouts OF THE SAME SYSTEM are usually caused by improper cleaning. If a severe burnout has
occurred, the oil will be black and acidic.
Table 30
DIP switch settings for humidifier control board (2- and 3-ton unit
Voltage
SW1
SW2
SW3
SW4
Amps
208/230
Off
On
Off
On
6.4
220/240
Off
On
Off
On
6.4
277
On
Off
Off
On
5.7
380/415
Off
Off
On
Off
3.7
460
On
On
Off
Off
3.4
!
WARNING
Risk of contacting caustic substances. Can cause injury.
Avoid touching or contacting the gas and oils with exposed skin. Severe burns will result.
Wear protective clothing, safety goggles and long rubber gloves when handling contaminated
parts.
!
WARNING
Risk of explosive discharge of high pressure refrigerant. Can cause serious injury.
This unit contains fluids and gasses under high pressure. Relieve pressure before working
with piping/connections.