Site Preparation and Installation
35
Liebert
®
Mini-Mate2
™
5.7.2 Piping Connections
Details for Refrigerant (R-407C) Loop piping are in
5.5.3 - Piping Connections and Coolant
Requirements
.
5.7.3 Electrical Connections
Refer
5.5.5 - Electrical Connections
for general wiring requirements and cautions. Refer to
electrical schematic when making connections.
Power Connections
The outdoor condensing unit requires its own power source and earth ground, with a disconnect
switch (field supplied) to isolate the unit for maintenance. A transformer is available for 277 VAC,
single phase, applications (2- and 3-ton).
Control Connections
Field-supplied control wires must be connected between the evaporator and the condensing unit. (See
Figure 16
and the electrical schematic on the units for more details.) Four wires are required
between the evaporator and condensing unit.
Table 19
Dimensions and net weights—air-cooled outdoor condensing units
Model Numbers
Dimensions, inches (mm)
Module Net
Weight
lb (kg)
60Hz
50Hz
A
B
C
PFH027A-L
—
40 (1016)
23-1/2 (597)
18 (457)
200 (91)
PFH027A-H
—
48 (1219)
31 (787)
18 (457)
241 (109)
PFHZ27A-L
—
PFH037A-L
PFH036A-L
PFH037A-H
PFH036A-H
53 (1343)
36-1/4 (918)
18 (457)
351 (159)
PFHZ37A-L
PFHZ36A-L
Source: DPN000130, Rev. 1