Microprocessor Control
49
Liebert
®
Mini-Mate2
™
Table 25
Equipment switch settings (unit control board)
Switch
OFF Position
ON Position
1
Compressor
Chill Water
2
Staged Reheat
SCR Reheat
3
Not Used--Must remain in OFF position
4
Not Used--Must remain in OFF position
5
Enable Reheat
Disable Reheat
6
Enable Humidifier
Disable Humidifier
7
Enable Dehumidifier
Disable Dehumidifier
8
Electric Reheat
Gas Reheat
Table 26
Switch settings (wall box board)
Switch
OFF Position
ON Position
1
Disable Beeper
Enable Beeper
2
Not Used--Must remain in OFF position
3
Not Used--Must remain in OFF position
4
Not Used--Must remain in OFF position
5
Not Used--Must remain in OFF position
6
Compressor on continuously
for tight control
Economy Mode
7
Disable Setback
Enable Setback
8
Enable Password
Disable Password