Site Preparation and Installation
Liebert
®
Mini-Mate2
™
36
Figure 21 General arrangement (air- cooled condensing unit)
5.8
Water and Glycol Cooled Condensing Unit
5.8.1 Location Considerations
The centrifugal fan air cooled condensing unit may be located above the dropped ceiling or any remote
indoor area. If noise is of concern, the condensing unit should be located away from personnel. Normal
operating sound may be objectionable if the condensing unit is placed near quiet work areas. Refer to
Table 9
for maximum refrigerant line lengths.
To mount the unit in the ceiling, refer to
5.5 - Installing the Ceiling Units
.
NOTE
Follow all national and local building, electrical and plumbing codes.
DPN000191
Rev. 2
*
*
Condenser
Coil
High Pressure
Switch
Scroll
Compressor
Hot Gas Bypass
Solenoid Valve
Hot Gas Bypass
Control V
alve
3/8" SAE 45° Male Flare
(MCD) or Atmospheric (PFH)
Pressure Relief Valve
Check
Valve
Sight Glass
Lee - Temp
Receiver
Liquid Line
Solenoid Valve
Liquid Injection
Valve Bulb
Suction Line Male Quick
Connect Coupling
3 - W
ay Head
Pressure
Relief V
alve
Liquid Line Male Quick
Connect Coupling
Liquid Line Female Quick
Connect Coupling
Expansion Valve
Liquid Injection
Valve
Service Access
Ports
Evaporator Coil
Suction Line Female Quick
Connect Coupling
External Equalizer
Sensing Bulb
Receiver
Heater
Pressure
Limiting
Switch
Pressure Balancing
Valve
* Use Liebert sweat adapter kit with field
hard piping or use Liebert pre-charged
line set. Close-coupling option
available with MCD.
Field Piping
Factory Piping