![Liebert Mini-Mate2 MCD24A Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/liebert/mini-mate2-mcd24a/mini-mate2-mcd24a_user-manual_1907294052.webp)
Microprocessor Control
Liebert
®
Mini-Mate2
™
44
6.2
Main Menu <Menu>
Press the MENU key to display the Main Menu. The Menu selections (in the following order) include:
Use the Up/Down arrow to scroll through the selections. When ready to select a particular function
press Enter.
6.3
Setpoints
Setpoints and system setup parameters are kept in nonvolatile memory. Selecting SETPOINTS from
the Main Menu will display the following selections:
• TEMPERATURE SETPOINT
• TEMPERATURE SENSITIVITY
• HUMIDITY SETPOINT
• HUMIDITY SENSITIVITY
• HIGH TEMPERATURE ALARM
• LOW TEMPERATURE ALARM
• HIGH HUMIDITY ALARM
• LOW HUMIDITY ALARM
Scroll through this submenu by using the Up/Down arrow, then press Enter to select a particular
function. To change a particular value, press Enter and use the Up/Down arrows to change the value.
When the value has been changed press Enter to store the value. For example to change the
temperature setpoint from the main status display.
1. Press the Menu key to display the main menu.
2. Scroll to “SETPOINTS” using the Up/Down arrow key. Press the Enter key.
3. Scroll to “TEMP SETPOINT” using the Up/Down arrow key. Press the Enter key.
4. Use the Up/Down arrow to change the value. Press the Enter key.
SETPOINTS
CALIBRATE SENSORS
STATUS
ALARM ENABLE
ACTIVE ALARMS
ALARM TIME DELAY
TIME
COMMON ALARM ENABLE
DATE
CUSTOM ALARMS
SETBACK
CUSTOM TEXT
SETUP OPERATION
DIAGNOSTICS
SETPOINT PASSWORD
END OF MENU
SETUP PASSWORD
Table 21
View default setpoints and allowable ranges
Setpoint
Default
Range
Temperature Setpoint
72°F
40-90°F (5-32°C)
Temperature Sensitivity
2.0°F
1-9.9°F (0.6-5.6°C)
Humidity Setpoint
50%
20-80% RH
Humidity Sensitivity
5%
1-30% RH
High Temperature Alarm
80°F
35-95°F (2-35°C)
Low Temperature Alarm
65°F
35-95°F (2-35°C)
High Humidity Alarm
60%
15-85% RH
Low Humidity Alarm
40%
15-84% RH