INSTALLATION INSTRUCTIONS
65
ENGLISH
NOTE
1. The above table shows the correlation between the air rates and E.S.P.
2. Be sure to set the value referring table 1. Unexpected set value will cause mal-function.
3. Table 1 is based at 230 V. According to the fluctuation of voltage, air flow rate varies.
Chassis
Capacity
(kBtu/h)
Grade
Step
CMM
Static Pressure [mmAq(Pa)]
0(0)
1(10)
2(20)
3(29)
4(39)
5(49)
Setting Value
32:01
32:02
32:03
32:04
32:05
32:06
L5
9
Standard
Compact
LOW
8
76
87
96
106
116
116
MID
9.5
87
96
106
114
120
120
HIGH
11.5
101
109
118
125
130
130
L5
12
Standard
Compact
LOW
8
76
87
96
106
116
116
MID
9.5
87
96
106
114
120
120
HIGH
11.5
101
109
118
125
130
130
L6
18
Standard
Compact
LOW
10
82
87
90
96
106
116
MID
12.5
92
98
105
109
119
128
HIGH
15
100
106
112
122
129
137
L3
24
Standard
Compact
LOW
12
89
95
102
106
120
130
MID
16
102
108
115
125
131
139
HIGH
20
125
131
136
141
142
147
L5
12
High
LOW
8
76
87
96
106
116
116
MID
9.5
87
96
106
114
120
120
HIGH
11.5
101
109
118
125
130
130
L3
18
High
LOW
10
80
90
95
100
110
120
MID
14
97
103
109
117
126
134
HIGH
18
115
122
127
133
138
142
Installer Setting - Static Pressure Step Setting
This function is applied to only duct type. Setting this in other cases will cause malfunction.
This function is only available on some products.
This is the function that static pressure of the product is divided in 11 steps for setting.
Ceiling Concealed Duct – Low static
Table 1
Содержание UM36FH
Страница 70: ...70 ENGLISH ...
Страница 71: ......