- 19 -
6. Heating Operation Mode(only Heating Model)
The unit will operate according to the setting conditions by the remote controller.
The operation diagram is shown below.
INTAKE AIR TEMP.
SETTING TEMP. +6°F
(Compressor OFF)
SETTING TEMP.
(Compressor ON)
Selecting
fan speed
Selecting
fan speed
A
B
A
minimum
10sec.
minimum
1 min.
minimum
10sec.
COMPRESSOR
ON
OFF
ON
OFF
• A point; While the indoor pipe temperature is higher than 95°F, indoor fan operates at low speed. When the
indoor pipe temperature becomes lower than 95°F, indoor fan stops.
• B point; When the indoor pipe temperature is higher than 38°C(100°F), fan operates at selected fan speed.
INDOOR FAN SPEED
Low
OFF
Low
Low
OFF
OFF
OFF
LOW
ON
Selecting
fan speed
INDOOR PIPE
TEMP.
82°F
78°F
1min
INDOOR FAN SPEED
COMPRESSOR
■
Hot-Start Control
• The indoor fan stops until the indoor pipe temperature will be reached at 82°F.
• During heating operation, if indoor pipe temperature falls below 78°F fan stops.
• The operation diagram is shown below.