Step 5. Verify the system configuration
After getting connected to the EnerBox2 through Soft AP mode, check the dashboard for the following. You
can also connect to EnerBox2 through the site’s routers.
A. Confirm that internet connection is secured.
B. Compare ‘Installed Number’ of AC modules with ‘Detected, Communicating or Producing Power’ of
AC modules. This number is refreshed in 15 min.
C. In areas like California, Hawaii or Molokai where Factory-installed grid profile(IEEE1547) is not
applied, users can edit grid profile by going [AC module - Set Grid Profile]. It takes 15 min for
updating changes.
D. Do ‘Start Scan’. If the number is matched, go on to next steps. If the number is more than input
number, delete MAC addresses that you cannot find from ‘Installation Map’.
EnerBox2 is connected to internet.
EnerBox2 is not connected to internet.
※ Make sure that the circuit breakers for branches where all of installed AC modules are attached are
surely turned on.
※ Power production data will be refreshed in 30 min at maximum.
The number is matched.
Go on to next steps.
The number is more than the input number.
Delete MAC addresses that you cannot find
from ‘Installation Map’.