AC Module System Installation Manual
Rev. 1.0
Connect the general AC cables in the following order:
There is a sample for AC output cables connection of single phase 208VAC below.
The micro inverter is compatible with 240VAC/120VAC and 208VAC/120VAC. No additional setting is required.
Step 1. Check your distribution panel for figuring out what type of AC distribution system you have. Use a volt-meter to
find out the phase and line-to-line voltage across L1, L2 and neutral. If the AC distribution system have 208VAC
for L1-L2 and 120VAC for L1-N and L2-N, the AC modules should not be connected more than 10 AC modules
per a 2-pole 20AMP circuit breaker as described above.
Step 2. Install an AC junction box on an appropriate position for a transition cable to reach to the last AC module. If
necessary, move the AC junction box close to the last AC modules.
Step 3. Check the extension/transition cables to verify they have not been pulled too tight or are hanging too loose.
Attach cables on a structure like PV racks or rails using the cable ties. Also, place extension/transition cables or
AC cables under a structure so that wires can avoid direct sunlight exposure and water immersion.
Step 4. Connect the equipment grounding conductor from all of the AC modules to the AC junction box ending to the
distribution panel.
Step 5. Make sure that a conduit or a small pipe protects wires from the AC junction box to the distribution panel from
rain, snow or direct sunlight.
transition cable
Conductor
Color
Description
L1
Black
Line to neutral voltage 120VAC
L2
Red
Line to neutral voltage 120VAC
Neutral
White
Neutral between L1 and L2
External Equipment Grounding Conductor (Array ↔ AC junction box)
Ground
Green
Conductor to connect normally non–current carrying metal parts of equipment together
General cable
L1
Black
Line to neutral voltage 120VAC
L2
Red
Line to neutral voltage 120VAC
L1-L2
-
Line to line voltage 208VAC
Neutral
White
Neutral between L1 and L2
Ground
Green
Conductor to connect normally non–current carrying metal parts of equipment together
X 10
Distribution panel
AC junction box
An array of AC modules
AC output single phase 208VAC
2-pole
20A
Meter
N L1 L2
G
41
Copyright © 2017 LG Electronics.
All Rights Reserved.
General Cable