Does the Operating LED of indoor unit blink
when Operation's ON?
Is the Connection between CN-Power of
indoor unit and terminal block?
Refer to the self-diagnosis function.
The Outdoor Unit does not operate at all.
Trouble 6
YES
Check the connecting state of connector
NO
NO
Is the connection of cable between indoor
and outdoor unit right?
Indoor
Outdoor
1(Brown)
1(Brown)
2(Blue)
2(Blue)
3(Green/YL)
3(Green/YL)
4(Red)
4(Red)
NO
YES
Is the voltage of CN-POWER
,
in out-
door PCB Ass'y about AC220V / 240V ?
Check the Fuse of Outdoor PCB Ass'y.
Check the connecting state of wires.
NO
YES
YES
Is the operation of outdoor Ass'y right?
(IC04D, IC01A)
Replace the parts.
NO
Replace the PCB Ass'y.
NO
Содержание HPCI-C35E
Страница 110: ... 110 Electronic Control Device 1 Room Type Indoor Unit MAIN P C B DC ASM MAIN P C B AC ASM ...
Страница 111: ... 111 2 Cassette Type Indoor Unit MAIN P C B DC ASM ...
Страница 112: ... 112 3 Convertible Type Indoor Unit ...
Страница 113: ...4 Duct Type Indoor Unit 9 12k 113 ...
Страница 114: ... 114 18k ...
Страница 115: ... 115 5 Display ASSY Room Type Indoor Unit Convertible Type Indoor Unit ...
Страница 116: ... 116 6 Outdoor Unit MAIN P C B ASM V P U N W ...
Страница 117: ... 117 Schematic Diagram 1 Room Type Indoor Unit ...
Страница 119: ... 119 3 Convertible Type Indoor Unit RY 4WAY RY OUTFAN ...
Страница 126: ... 126 354212 249951 268714 266012 352114 263230 352118 330870 158591 3 Cassette Type Indoor Unit 12K 18K Btu Models ...
Страница 127: ... 127 346810 130411 359011 152312 135802 135312 2 W0CZZ 137211 267110 352150 352150 130911 268712 146811 ...
Страница 139: ...P No 3828A20097S February 2004 Printed in Korea ...