-20-
Operation Details
1. Room Type Indoor Unit
(1) The Function of main control
• DISPLAY
Operation Indicator
• On while in appliance operation, off while in appliance pause
• Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)
Sleep Timer Indicator
• On while in sleep timer mode, off when sleep timer cancel or appliance operation pause
Timer Indicator
• On while in timer mode (on/off), off when timer mode is completed or canceled
Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control
■
Cooling Mode Operation
• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan
stop.
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp
➲
Setting Temp+0.5°C
Compressor OFF Temp
➲
Setting Temp-0.5°C
• While in compressor running, operating with the airflow speed set by the remote control. While in compressor
not running, operating with the low airflow speed regardless of the setting.
■
Soft Dry Operation Mode
• When the dehumidification operation input by the remote control is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C
≤
Intake Air Temp
➲
25°C
24°C
≤
Intake Intake Air Temp<26°C
➲
Intake Air Temp-1°C
18°C
≤
Intake Intake Air Temp<24°C
➲
Intake Air Temp-0.5°C
Intake Air Temp<18°C
➲
18°C
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat.
Compressor ON Temp.
➲
Setting Temp+0.5°C
Compressor OFF Temp.
➲
Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
■
Heating Mode Operation
• When the intake air temp r3°…above the setting temp, the compressor is turned off. When below
the setting temp, the compressor is turned on.
Compressor ON Temp.
➲
Setting Temp.
Compressor OFF Temp.
➲
Setting Temp.+3°C
• While in compressor on, the indoor fan is off when the indoor pipe temp. is below 26°C, when above 28°C , it
operates with the low or setting airflow speed.
Содержание HPCI-C35E
Страница 110: ... 110 Electronic Control Device 1 Room Type Indoor Unit MAIN P C B DC ASM MAIN P C B AC ASM ...
Страница 111: ... 111 2 Cassette Type Indoor Unit MAIN P C B DC ASM ...
Страница 112: ... 112 3 Convertible Type Indoor Unit ...
Страница 113: ...4 Duct Type Indoor Unit 9 12k 113 ...
Страница 114: ... 114 18k ...
Страница 115: ... 115 5 Display ASSY Room Type Indoor Unit Convertible Type Indoor Unit ...
Страница 116: ... 116 6 Outdoor Unit MAIN P C B ASM V P U N W ...
Страница 117: ... 117 Schematic Diagram 1 Room Type Indoor Unit ...
Страница 119: ... 119 3 Convertible Type Indoor Unit RY 4WAY RY OUTFAN ...
Страница 126: ... 126 354212 249951 268714 266012 352114 263230 352118 330870 158591 3 Cassette Type Indoor Unit 12K 18K Btu Models ...
Страница 127: ... 127 346810 130411 359011 152312 135802 135312 2 W0CZZ 137211 267110 352150 352150 130911 268712 146811 ...
Страница 139: ...P No 3828A20097S February 2004 Printed in Korea ...