-24-
■
Forced Operation
• To operate the appliance by force in case that the remote control is lost, the forced operation selection switch
is on the main unit of the appliance to operate the appliance in the standard conditions.
• When the power is supplied while the slide switch is on the forced operation position, or when the slide switch
position is switched to the Auto Restarting (or test operation) position or switched from the remote control
position to the forced operation position while the power is on, the forced operation is carried out.
• When the slide switch position is switched from the forced operation position to the Auto Restarting position or
the remote control position, the forced operation is canceled and the appliance stops operating.
• In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the opera-
tion condition is set according to the intake air temperature as follows.
24°C
≤
Intake Air Temp
➲
Cooling Mode Operation, 22°C, High Speed
21°C
≤
Intake Air Temp<24°C
➲
Dehumidification Operation, 23°C, High Speed
Intake Air Temp<21°C
➲
Heating Mode Operation, 24°C, High Speed
■
Remote Control Operation Mode
• When the remote control is selected by the slide switch on the main unit, the appliance operates according to
the input by the remote control.
■
Protection of the evaporator pipe from frosting
• If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool-
ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor
evaporator pipe from frosting.
• When the indoor pipe temp is 7°C and higher after 3 min. pause of the compressor, the compressor and the
outdoor fan is turned on according to the condition of the room temperature.
■
Buzzer Sounding Operation
• When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
• When the appliance-pause key is input by the remote control, the long "beep—" sounds.
Содержание HPCI-C35E
Страница 110: ... 110 Electronic Control Device 1 Room Type Indoor Unit MAIN P C B DC ASM MAIN P C B AC ASM ...
Страница 111: ... 111 2 Cassette Type Indoor Unit MAIN P C B DC ASM ...
Страница 112: ... 112 3 Convertible Type Indoor Unit ...
Страница 113: ...4 Duct Type Indoor Unit 9 12k 113 ...
Страница 114: ... 114 18k ...
Страница 115: ... 115 5 Display ASSY Room Type Indoor Unit Convertible Type Indoor Unit ...
Страница 116: ... 116 6 Outdoor Unit MAIN P C B ASM V P U N W ...
Страница 117: ... 117 Schematic Diagram 1 Room Type Indoor Unit ...
Страница 119: ... 119 3 Convertible Type Indoor Unit RY 4WAY RY OUTFAN ...
Страница 126: ... 126 354212 249951 268714 266012 352114 263230 352118 330870 158591 3 Cassette Type Indoor Unit 12K 18K Btu Models ...
Страница 127: ... 127 346810 130411 359011 152312 135802 135312 2 W0CZZ 137211 267110 352150 352150 130911 268712 146811 ...
Страница 139: ...P No 3828A20097S February 2004 Printed in Korea ...