Service Manual 53
Troubleshooting Guide
Evacuation
(All amount of refrigerant leaked)
• Procedure
(1) Connect the vacuum pump to the center hose
of charge set center hose
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
tely 5 minutes after turning off the vacuum
pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed.
Lo
Open
Open
Vacuum pump
3-Way
valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way
valve
CLOSE
OPEN
Содержание AS-W0964DH0
Страница 64: ...Service Manual 69 Schematic Diagram Models AS W1865DH0 AS W1825DH0 Models AS W096E1G0 AS W126E1G0 ...
Страница 66: ...Service Manual 71 BOTTOM VIEW TOP VIEW Schematic Diagram Models AS W0964DH0 AS W0964GH0 ...
Страница 70: ...Service Manual 75 Schematic Diagram DISPLAY ASSEMBLY 6871A20574A 6871A20624A ...
Страница 84: ...P No 3828A20462G October 2006 Printed in Korea ...