Service Manual 55
Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Temp. difference : approx. 0°C
Current : less than 80% of
rated current
Temp. difference : approx. 8°C
Current : less than 80% of
rated current
Temp. difference : less than 8°C
Current : over the reated
current
Temp. difference : over 8°C
Operating Current
• All amount of refrigerant leaked
out. Check refrigeration cycle.
• Refrigerant leakege
Clog of refrigeration cycle
Defective compressor
• Excessive amount of refrigerant
• Normal
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower tem-
perature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
1. The suction pressure is usually 8.5~9.5kg/cm
2
G(Cooling) at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
NOTICE
NOTICE
Suction pressure
Temperature
(Compared with
(Compared with
Cause of Trouble
Description
the normal value)
the normal valve)
Defective compressor
Current is low.
Defective 4-way reverse valve
Excessive amount of
High pressure does not quickly
Normal
refrigerant
rise at the beginning of
operation.
Insufficient amount of
Current is low.
Lower Higher
refrigerant
(Leakage)
Clogging
Current is low.
High
Higher
Cycle Parts
Содержание AS-W0964DH0
Страница 64: ...Service Manual 69 Schematic Diagram Models AS W1865DH0 AS W1825DH0 Models AS W096E1G0 AS W126E1G0 ...
Страница 66: ...Service Manual 71 BOTTOM VIEW TOP VIEW Schematic Diagram Models AS W0964DH0 AS W0964GH0 ...
Страница 70: ...Service Manual 75 Schematic Diagram DISPLAY ASSEMBLY 6871A20574A 6871A20624A ...
Страница 84: ...P No 3828A20462G October 2006 Printed in Korea ...