Service Manual 65
Troubleshooting Guide
8
• Indoor fan is locked or separated
• Fan connector is not connected to indoor pcb assembly
• Defective in DC-fan driving circuit
Indoor fan is locked
(BLDC fan model only)
Indoor fan is rotating ? (1)
Indoor fan is rotating ? (2)
YES
No
Check indoor unit
- remove obstacles in
indoor unit
- fan assembled correctly.
No
Check soldering state of
CN-Motor1 & assembling
state of DC Fan connector
Check flow
DC–fan driving circuit is right ?
YES
No
Check DC Fan Driving circuit
(Soldering state & Direction)
- R01F~R09F, C01F~C03F,
IC01F~IC03F, Q01F~Q02F, ZD01F
9
• Outdoor fan is locked by an obstacle (ex : branch of tree, bar…etc)
• Fan connector is not connected to outdoor pcb assembly
• Defective in DC-fan driving circuit
Outdoor fan is locked
(BLDC fan model only)
Outdoor fan is rotating ? (1)
Outdoor fan is rotating ? (2)
YES
No
Check outdoor unit
- remove obstacles in
outdoor unit
No
Check connector is not
connected to outdoor pcb
assembly (CN-FAN2)
Check flow
DC–fan driving circuit is right ?
YES
No
Check DC Fan driving circuit
(Soldering state & Direction)
- R01F~R05F, C01F~C03F,
Q01F~Q04F, ZD01F
Description
Cause of error
Error code
Description
Cause of error
Error code
Содержание AS-W0964DH0
Страница 64: ...Service Manual 69 Schematic Diagram Models AS W1865DH0 AS W1825DH0 Models AS W096E1G0 AS W126E1G0 ...
Страница 66: ...Service Manual 71 BOTTOM VIEW TOP VIEW Schematic Diagram Models AS W0964DH0 AS W0964GH0 ...
Страница 70: ...Service Manual 75 Schematic Diagram DISPLAY ASSEMBLY 6871A20574A 6871A20624A ...
Страница 84: ...P No 3828A20462G October 2006 Printed in Korea ...