System Set-Up
ENGLISH
Hydro Kit
Installation Manual
39
Summary
Example of Fuction Code Display
Function Code
Value #1
Value #2
Function
Default
Value #1
Value #2
Remark
Disable 3 Min. Delay
02:01
01
-
Remote Air Sensor Connection
03:01
01 : NOT connected.
02 : connected.
-
Celsius/Fahrenheit Switching
04:01
01 : Celsius
02 : Fahrenheit
-
Setting Temp. Selection
05:02
01 : Air Temp.
02 : Leaving water Temp.
-
Auto Dry Contact
06:01
01 : Auto Start OFF
02 : Auto Start ON
-
Address Setting
07:00
00 ~ FF
-
Override Setting
08:00
00 : Slave
01 : Master
-
Water Pump Test Run
09:00
01 : Set
-
Setting Air Temp.
(Heating Mode)
13:030:016
24℃(75℉) ~ 30℃(86℉)
: Upper Limit of setting range
16℃(60℉) ~ 22℃(71℉)
: Lower Limit of setting range
Setting Leaving Waer Temp.
(Heating Mode)
14:080:046
50℃(122℉) ~ 80℃(176℉)
: Upper Limit of setting range
30℃(86℉) ~ 46℃(114℉)
: Lower Limit of setting range
Setting Sanitary Tank Water Temp.
(Sanitary Water Heating)
15:080:046
50℃(122℉) ~ 80℃(176℉)
: Upper Limit of setting range
30℃(86℉) ~ 46℃(114℉)
: Lower Limit of setting range
Setting outdoor Temp. range
(Weather-dependent operation)
23:-10:015
10℃(50℉) ~ 20℃(68℉)
: Upper Limit of setting range
-20℃(-4℉) ~ 05℃(41℉)
: Lower Limit of setting range
Setting indoor air Temp. range
(Weather-dependent operation)
24:021:016
20℃(68℉) ~ 30℃(86℉)
: Upper Limit of setting range
16℃(60℉) ~ 19℃(66℉)
: Lower Limit of setting range
Setting leaving water Temp.
(Weather-dependent operation)
25:080:046
65℃(149℉) ~ 80℃(176℉)
: Upper Limit of setting range
40℃(104℉) ~ 54℃(129℉)
: Lower Limit of setting range
Setting start/maintain time
(Disinfection Operation)
26:000
00 : Disable
01 : Enable
-
26:006:023
01~07 : Starting Date
(01:Sun, 02:Mon, ····, 07:Sat)
00~23 hours
: Starting Time in 24 hours
Setting Temp.
(Disinfection Operation)
27:070:010
40℃(104℉) ~ 70℃(129℉)70
: Maximum heating Temp.
05~60 min
: Maximum heating duration
Setting control parameter
(Sanitary water heating operation)
28:005:080
01℃(33℉) ~ 20℃(68℉)
: Temp. gap from Value #2
50℃(122℉) ~ 80℃(176℉)
Setting control parameter
(Sanitary water heating operation)
29:003:000
02℃(35℉) ~ 04℃(39℉)
00~01 :Refer to 46p
Setting sanitary water heating timers
2b:030
5 ~ 95 min (step: 5 min)
-
2b:180:020
0 ~ 600 min (step: 30 min)
20 ~ 95 min (step: 5 min)
Changing thermal on/off room air
Temp.
2E:00
00~03 : Refer to 46p
-
Changing thermal on/off leaving
water Temp.
2F:00
00~03 : Refer to 46p
-
Program version
30:00
Display Version number
-
Changing thermal on/off sanitary tank water Temp. 33:00
00~03 : Refer to 47p
-
Select entering/leaving water Temp
mode in Heating Mode
34:00
00 : Based on leaving water Temp
01 : Based on entering water Temp
-
Select entering/leaving water Temp
mode in Cooling Mode
35:00
00 : Based on leaving water Temp
01 : Based on entering water Temp
-
*Temp. = Temperature
Содержание ARNH08GK3A2
Страница 49: ......