Installation
ENGLISH
Hydro Kit
Installation Manual
15
PT 1/2 inch
Process PT 1/2 inch
female bolt
Inside water tank
Water tank outer wall
Water Tank
Temperature Sensor
Sensor
holder
• If hot water mode is used, make sure to install
sensor to water tank.
• Make PT15A female bolt hole in the water tank,
and install sensor in the water tank.
• Push the sensor into the hole of the sensor holder
cap.
• Lock the sensor holder cap.
Water tank temperature sensor connection
WARNING :
Installing recirculation pump
When Hydro Kit is used with the sanitary water tank, it is STRONGLY recommended to install
recirculation pump to prevent cold water at the end of hot water supply flooding out and to
stabilize the water temperature inside the sanitary water tank.
- The recirculation pump should be operated when sanitary water demand is not required.
Therefore, external time scheduler to determine when the recirculation pump should turn on
and turn off is required.
- The operating duration time of the recirculation pump is calculated as follow :
Duration time [minute] = k * V / R
k : 1.2 ~ 1.5 is recommended.
(If distance between pump and tank is far, then choose high number.)
V : Volume of sanitary water tank [liter]
R : Water flow rate of pump [liter per minute], which is determined by pump performance
curve.
- The pump operating start time should be prior to the sanitary water demand.
Sanitary
Water Tank
Recirculation
Pump
External
Time Scheduler
Shower
(End of Hot
water supply)
Hot water supply
City water
Water In
Water Out
Содержание ARNH08GK3A2