• Function Code 2B
: Setting sanitary water heating timers
Determine time duration : Operation time and stop time of sanitary tank heating.
- Value #1 of Function Code 2B : This time duration defines how long sanitary tank heating
can be continued.
- Value #2 of Function Code 2B : This time duration defines how long sanitary tank heating
can be stopped. It is also regarded as time gap between
sanitary tank heating cycle.
- Example of timing chart :
Sanitary tank
heating is enabled
Sanitary tank
heating is required
Sanitary tank
heating operation
Time
2B.01
2B.01
2B.02
2B.02
2B.02
System Set-Up
44
Hydro Kit
• Function Code 28 and 29
: Setting control parameter for Sanity water heating operation
Descriptions for each parameters are as following.
- Value #1 of Function Code 28 : temperature gap from Value #2 of Function Code 28.
- Value #2 of Function Code 28 : maximum temperature.
- Example : If Value #1 is set as ʻ5ʼ and Value #2 is set as ʼ80ʼ, then water tank heating will be
started when the water tank temperature is below 75°C(167°F).
- Value #1 of Function Code 29 : temperature gap from target sanitary water temperature.
- Value #2 of Function Code 29 : Determining heating demand priority between sanitary water
tank heating and under floor heating.
- Example : If userʼs target temperature is set as ʼ50ʼ and Value #1 is set as ʻ3ʼ, then water
tank heating will be turned off when the water temperature is above 53°C(127°F).
Water tank heating will be turned on when the water temperature is below
50°C(122°F).
- Example : If Value #2 is set as ʻ0ʼ, that means heating priority is on sanitary water heating, In
this case the under floor can not be heated while sanitary water heating. On the
other hand, if the Value #2 is set as ʻ1ʼ, that means heating priority is on under
floor heating, sanitary tank can not be heated while under floor heating.
Sanitary water heating does not operate when it is disabled.
Enabling / Disabling sanitary water heating to operate is determined by pushing button.
When icon is displayed on the remote controller, sanitary water heating is enabled.
(by button input or scheduler programming)