Product Data 40
YA Chassis
PTAC
6RWU0-06A
• Electrical Controls
Error
Code
Descriptions
Cause of Error
Check Point
01
Indoor unit room temperature
sensor error
• The Indoor Air Thermistor Error
occurs when the indoor temperature
is ≤-35°C or ≥100°C.
• Check the error after change sensor.
• Check the insertion of PCB Connector
Wafer.
02
Indoor unit inlet pipe sensor error
• The Indoor Coil Thermistor Error
occurs when the indoor pipe
temperature is ≤ -35°C or ≥ 100°C.
• Check the error after change sensor.
• Check the insertion of PCB Connector
Wafer.
03
Wired remote control error
• Interference (Twisted / Non-
separation) of AC Line and wired
remote control line
• Poor contact / Disconnection of
wired remote control (DC Line) and
PCBA harness
• PCBA harness flooding / corrosion
• Remote control fault
• Indoor unit PCBA fault
• Check the molding status of the wired
remote control wire.
• Check the interference status with DC
line (Twisted / Mixed / Non-separation)
• Check communication cable problem
• Check harness Flooding / corrosion
• Check Remote control fault
• Check Indoor unit PCBA fault
05
Communication error between
indoor and outdoor units
• No power on indoor unit
• Indoor/outdoor unit power
connection error / communication
line not installed
• unit communication Communication
error caused by external noise
• Indoor/outdoor circuit parts burned
• Disconnection of the transmission
connection
• Improper connection of terminal block
communication wire
• Improper wiring of communication L-N
wire (indoor /outdoor unit
communication wire)
• No power supply due to indoor /
outdoor unit PCBA burn
07
Thermostat Wiring Error
• The Thermostat Wiring Error has
occurred if the PTAC receives
control commands that cannot be
driven from the Thermostat.
• Check the connection with Themostat
comparing with manual.
09
Indoor unit EEPROM error
• The EEPROM Check Sum Errors
occurs when the original check sum
and calculated check sum do not
match.
• Check the insertion of EEPROM.
• Unplug and plug the power code
10
Indoor unit BLDC motor fan lock
• The Indoor Fan Error occurs when
there is not feedback signal from
Hall sensor located in BLDC Motor
in 50 seconds delay time or
feedback signal lower than 50RPM
(applied in models using the BLDC
Motor).
• Check the insertion of BLDC
Connector.
• Check whether the output voltage
between the two terminals 4-5pins in
CN-MOTOR-ODF is 15V.
• Check whether the output voltage
between the two terminals 4-6pins is
over 2V.
• Check whether the output voltage
between the two terminals 4-7pins is
exist or not.
21
DC Peak (IPM Fault)
• Over load operation (indoor /
outdoor fan constraint, screened,
blocked, cycle issue)
• Refrigerant leak
• Disconnection / shot-circuit inside
compressor Compressor failure
• Burned parts inside PCBA (IPM
failure)
• Check indoor / outdoor fan constraint,
screened / flow structure
• Check refrigerant leakage
• Check compressor wire open/short
• Check compressor insulation damage
• Check if IPM burned