33 Product Data
YA Chassis
PTAC
6RWU0-06A
1.8 Electrical characteristics
Notes :
1. Voltage range Voltage supplied to the unit terminals should be
within the minimum and maximum range.
2. Maximum allowable voltage unbalance between phase is 2 %.
3. Select wire spec. based on the larger value of MCA.
4. RLA is measured during each individual compressor test
condition.
5. IFM & OFM is measured as the outdoor unit test condition.
6. Recommended circuit breaker is ELCB (Earth Leakage Circuit
Breaker)
MCA : Minimum Circuit Amperes (A)
MOP : Maximum Rating Over Current Protective Device (A)
RLA : Rated Load Amperes (A)
FLA : Full Load Amperes (A)
OFM : Outdoor Fan Motor
IFM : Indoor Fan Motor
Unit
Power
Compressor
Motor FLA
Model
Type
Hz
Voltage
Voltage Range
MCA
MOP
RLA
IFM
OFM
LP073IHP.AK3GEUS(Y4NV07ANLK0.AK3GEUS)
Inverter
60
208~230
Min : 187
Max : 253
11.9/ 17.2/ 28.0
15/ 20/ 30
5.16
0.11
0.45
LP093IHP.AK3GEUS(Y4NV09ANLK0.AK3GEUS)
11.9/ 17.2/ 28.0
15/ 20/ 30
5.16
0.11
0.45
LP123IHP.AK3GEUS(Y4NV12ANLK0.AK3GEUS)
11.9/ 17.2/ 28.0
15/ 20/ 30
6.15
0.29
0.63
LP153IHP.AK3GEUS(Y4NV15ANLK0.AK3GEUS)
11.9/ 17.2/ 28.0
15/ 20/ 30
6.15
0.29
0.63