General information 19
PTAC
6RWU0-06A
Compressor Restart Delay
This feature extends the overall life of the compressor by preventing the short cycling of the air-conditioner. When the com-
pressor restarts, LG PTAC is designed to give it a minimum of three minutes to have a time of equalizing the refrigerant
pressures for optimizing the cycle.
Fan Only Setting
When the Fan only setting is made, only the fan on the indoor side operates while the compressor stops operating and the
unit ceases to run in the Cooling or the Heating mode.
Indoor Fan Speed Setting
The Indoor fan can run at Slo,Low,Med or High speed for either COOLING or HEATING operation.
Two Fan Motors
The air conditioning unit has dual BLDC motor, one is for indoor fan and other one for outdoor fan for providing a quiet oper-
ation and maximum efficiency.
LED Diagnostics and Self Diagnostics
LED Diagnostics feature indicates the problem by its easy to read diagnostics, when the unit does not operate properly. For
example, one blink every 2 seconds indicates compressor failure.
While Self Diagnostics feature is used in micom models and it indicates the problem by displaying a set of error codes.
Indoor Room Freeze Protection
When the unit senses the room temperature to be less than 40˚ F, the unit activates the fan motor and either the electric
resistance heater or the hydronic heater, to prevent the pipes or fixtures from freezing. This also overrides the front desk
control of the unit mounted controls or the wall mounted controls.
Compressor Overload Protection
This feature prevents damage of the compressor by sensing the indoor coil temperature during the heating mode. If the
indoor coil temperature is over 54℃(130℉), the outdoor fan is switched off and it operates again only when the temperature
drops below 49℃(120℉).
Features
Содержание AK3GEUS
Страница 1: ...6RWU0 06A PTAC Type 60Hz R410A ...
Страница 10: ...10 General information PTAC 6RWU0 06A ...
Страница 55: ...55 Installation Installation of unit 6RWU0 06A PTAC ...