Self-diagnosis Function
Installation Manual
41
ENGLISH
Indoor Unit Error
Ex) Error 03 (Remote controller error)
Dip Switch Setting
3 Times
3 Times
3 Times
2 Seconds.
LED02G
(GREEN)
2 Seconds.
Indoor PCB
Indoor PCB
Indoor PCB
Function
Description
Setting Off
Setting On
Default
SW3
Group Control
Selection of Master or Slave
Master
Slave
Off
SW4
Dry Contact Mode
Selection of Dry Contact
Mode
Wired/Wireless remote
controller
Selection of Manual or Auto
operation Mode
Auto
Off
SW5
Installation
Fan continuous operation
Continuous operation
Removal
Working
Off
01 Indoor Room sensor error 0 1time
◑
OFF
02 Indoor in-pipe sensor error 0 2times
◑
OFF
03 Remote controller error 0 3times
◑
OFF
04 Drain pump error 0 4times
◑
OFF
05 Communication error indoor and outdoor 0 5times
◑
OFF
06 Indoor out-pipe sensor error 0 6times
◑
OFF
09 EEPROM error (indoor) 0 9times
◑
OFF
10 BLDC motor fan lock (indoor) 1time
◑
0 OFF
Error Code
Description
LED 1
(Red)
LED 2
(Green)
Indoor
status
h
Because remote controller turn off when occur ERROR in simultaneous operation system, it
should check LED blinks of outdoor in order to confirm error code.
h
Repeatedly after LED1 is turned on and off as the Error code number of tens digit, LED2 is
turned on and off as the Error code number of single-digit.
Self-diagnosis Function
1,MFL67939921,영영 2018. 8. 2. 영영 1:41 Page 41