How to Set E.S.P?
Installation Manual
39
ENGLISH
Ceiling Concealed Duct – H-INV
Table 3
Model
Step
CMM
[m
3
/min]
Static Pressure [mmAq (Pa)]
4(39)
5(49)
6(59)
8(78)
10(98)
12(118)
Setting Value
32:01
32:02
32:03
32:04
32:05
32:06
ABNW36GBRH0
LOW
21
68
72
78
84
91
97
MID
28
75
79
84
89
95
101
HIGH
34
81
85
88
94
100
105
Model
Step
CMM
[m
3
/min]
Static Pressure [mmAq (Pa)]
4(39)
5(49)
6(59)
8(78)
10(98)
12(118)
Setting Value
32:01
32:02
32:03
32:04
32:05
32:06
ABNW42GBRH0
LOW
24
75
79
86
93
98
MID
31
81
85
91
98
103
HIGH
37
88
91
97
102
107
Model
Step
CMM
[m
3
/min]
Static Pressure [mmAq (Pa)]
4(39)
5(49)
6(59)
8(78)
10(98)
12(118)
Setting Value
32:01
32:02
32:03
32:04
32:05
32:06
ABNW48GBRH0
LOW
28
79
84
89
95
101
MID
34
85
88
94
100
105
HIGH
40
91
93
99
105
110
NOTE
Be sure to set the value referring table 3. Unexpected set value will cause mal-function.
As far as possible do not set ESP 82,83
Table 3 is based at 230 V. According to the fluctuation of voltage, air flow rate varies.