36
How to Set E.S.P?
Note :
1. The above table shows the correlation between the air rates and E.S.P.
2. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.
3. Table 1 is based at 230 V. According to the fluctuation of voltage, air flow rate varies.
Ceiling Concealed Duct – Low static
Table 1
Model
Step
CMM
[m
3
/min]
Static Pressure [mmAq (Pa)]
0(0)
1(10)
2(20)
3(29)
4(39)
5(49)
Setting Value
32:01
32:02
32:03
32:04
32:05
32:06
ABNH09GL1A2
LOW
5.5
69
76
83
91
101
111
MID
7
81
87
94
101
109
117
HIGH
9
97
103
108
117
124
131
Model
Step
CMM
[m
3
/min]
Static Pressure [mmAq (Pa)]
0(0)
1(10)
2(20)
3(29)
4(39)
5(49)
Setting Value
32:01
32:02
32:03
32:04
32:05
32:06
ABNH12GL2A2
LOW
7
78
82
87
93
100
107
MID
8.5
87
91
94
100
108
116
HIGH
10
96
100
103
109
117
125
Model
Step
CMM
[m
3
/min]
Static Pressure [mmAq (Pa)]
0(0)
1(10)
2(20)
3(29)
4(39)
5(49)
Setting Value
32:01
32:02
32:03
32:04
32:05
32:06
ABNH18GL2A2
LOW
10
96
100
103
109
117
125
MID
12.5
109
113
117
123
130
137
HIGH
15
120
124
129
134
141
147
Model
Step
CMM
[m
3
/min]
Static Pressure [mmAq (Pa)]
0(0)
1(10)
2(20)
3(29)
4(39)
5(49)
Setting Value
32:01
32:02
32:03
32:04
32:05
32:06
ABNH24GL3A2
LOW
12
89
95
102
106
120
130
MID
16
102
108
115
125
131
139
HIGH
20
125
131
136
141
144
147
1,MFL67939921,영영 2018. 8. 2. 영영 1:41 Page 36
Содержание ABNW70GB9A0
Страница 42: ...42 1 MFL67939921 영영 2018 8 2 영영 1 41 Page 42 ...
Страница 43: ...1 MFL67939921 영영 2018 8 2 영영 1 41 Page 250 ...