Installation Manual
27
Optional Operation
ENGLISH
Installer Setting - Setting Address of Central Control
This function is to be used when connecting to a central controller.
See the central controller manual for more detailed functions.
Press and hold
B
button for more than 3 seconds to enter the installer settings mode.
- If pressing only once briefly, it will enter the user settings mode.
Make sure to press and hold for more than 3 seconds.
Once entered the address setting mode using
B
button, it displays as below.
Code value
Group number
Indoor unit number
Set the group No. using
F G
button. (0~F)
Move to the indoor unit No. set value using
H I
button.
Set the indoor unit No. value using
F G
button. (0~F)
Press
K
button to complete the address setting.
Press
L
button to exit.
h
If no button is selected for about 25 seconds after setup, it exits the setup mode automatically.
h
If the
K
button is not selected before you exit, the changes will not apply.