Chapter 5 System Operation
890 USE 120 00
93
Procedure for Verifying System Operation, continued
Quick Tuning
Procedure
This procedure will enable you to rapidly assess the operational readiness of the
system.
Continued on next page
Step
Action
1
Disconnect the drive from the power source.
WARNING!
MECHANICAL MOVEMENT HAZARD
Ensure the motor is securely mounted and that the load is disconnected
from the motor.
Failure to observe this precaution can result in severe injury or
equipment damage.
2
Ensure 0 V is applied to the enable input (connector X3, terminal 15).
3
Connect the PC to the drive via the serial communications cable.
4
Turn on the 24 Vdc bias supply. After the initialization procedure
(< 5 seconds) the status is shown in the LED display.
5
Switch on the PC, start the UniLink software and select the serial
communication port to which the drive is connected. (The parameters that
are stored in the SRAM of the drive are transferred to the PC.)
6
Use the UniLink software to check/establish the following:
l
Drive Parameters - Set/restore the drive parameters to the factory
default values
l
Supply voltage - Set the supply voltage to the actual mains supply
voltage
l
Servo Motor - Select the applicable BPH servo motor.
l
Feedback - Ensure the feedback matches the feedback unit in the
servo motor
Содержание MHDA1004
Страница 1: ...Version 2 0 June 2003 31001643_K01_000_04 Lexium Servo Drive 17D Series User Guide...
Страница 2: ......
Страница 4: ...Preface iv 890 USE 120 00...
Страница 14: ...Contents xiv 890 USE 120 00...
Страница 28: ...14...
Страница 46: ...32...
Страница 56: ...42...
Страница 112: ...Chapter 5 System Operation 98 890 USE 120 00...
Страница 130: ...116 Continued on next page...
Страница 148: ...134...
Страница 172: ...158...
Страница 198: ...184...
Страница 204: ...Index 190 890 USE 120 00...