CAN bus cable
To meet ISO 11898 you should use a bus cable with a characteristic impedance of
120
Ω
. The maximum usable cable length for reliable communication decreases
with increasing transmission speed. As a guide, you can use the following values
which we have measured, but they are not to be taken as assured limits:
Cable data:
Characteristic impedance
100-120
Ω
Cable capacitance
max. 60 nF/km
Lead resistance (loop)
159.8
Ω
/km
Cable length, depending on the transmission rate
Lower cable capacitance (max. 30 nF/km) and lower lead resistance (loop,
115
Ω
/km) make it possible to achieve greater distances.
(Characteristic impedance 150 ± 5
Ω
=:> terminating resistor 150 ± 5
Ω
).
For EMC reasons, the SubD connector housing must fulfill the following conditions:
l
metal or metallized housing
l
shield connection to housing.
Transmission rate (kBauds)
max. cable lenght (m)
1000
20
500
70
250
115
*
6 1
5
9
6 1
5
9
6 1
5
9
6 1
5
9
X6
X6
X6
X6
CANL
CANH
PGND
Shield
CANL
CANH
PGND
Shield
*
* about 120
Ω
according to line impedance
Содержание MHDA1004
Страница 1: ...Version 2 0 June 2003 31001643_K01_000_04 Lexium Servo Drive 17D Series User Guide...
Страница 2: ......
Страница 4: ...Preface iv 890 USE 120 00...
Страница 14: ...Contents xiv 890 USE 120 00...
Страница 28: ...14...
Страница 46: ...32...
Страница 56: ...42...
Страница 112: ...Chapter 5 System Operation 98 890 USE 120 00...
Страница 130: ...116 Continued on next page...
Страница 148: ...134...
Страница 172: ...158...
Страница 198: ...184...
Страница 204: ...Index 190 890 USE 120 00...