Mounting, removal and electrical installation
Leuze electronic
MSI 100/200
63
7.2
Mounting
7.2.1
Mounting instructions
7.2.2
Mounting location
•
Mount the module in a dust- and humidity-protected switch cabinet or terminal box (IP54
or higher).
•
Secure the switch cabinet/terminal box against opening by unauthorized persons.
ATTENTION: Property damage
Improper mounting can result in property damage.
•
When mounting the MSI 100/200 system, observe the following instructions.
Table 7-1
Important mounting instructions
Connection via DIN rail connectors
MSI-TBUS
To connect the MSI 100 and MSI 200 safety modules as well as the MSI-EM200-8I4IO and
MSI-EM200-4RO safe extension modules, use only the yellow MSI-TBUS DIN rail connec-
tor.
Connection with another DIN rail connector is not permitted.
TBUS
For the connection of non-safe extension devices (gateways), use only the green TBUS
DIN rail connector.
Connection with another DIN rail connector is not permitted.
Mounting direction for extensions
Non-safe extension:
left
Mount a non-safe extension module (gateway) to the left of the MSI 100 or MSI 200 safety
module.
Safe extension:
right
Mount the MSI-EM200-8I4IO and/or MSI-EM200-4RO safe extension modules to the right
of the MSI 200 safety module.
Maximum number of extension devices
Non-safe extension
Connect a maximum of one non-safe extension device (gateway) to the MSI 100 or
MSI 200 safety module.
Safe extension
Connect a maximum of ten safe extension modules to the MSI 200 safety module.
You can find a graphical depiction of an MSI 100/200 system extended with MSI-TBUS and
TBUS in Figure 2-2 on page 17.