Technical data and ordering data
Leuze electronic
MSI 100/200
107
14.2
Technical data MSI-EM200-8I4IO
Logic / supply
Rated control circuit supply voltage U
S
Permissible range
24 V DC (supply via MSI-TBUS)
18 V DC … 30 V DC
(incl. all tolerances, incl. residual ripple)
Rated control supply current I
S
(supply via MSI-TBUS)
Typ. 51.6 mA
(no inputs and outputs set, A1/A2 open)
Typ. 66 mA
(all inputs and safe outputs set)
Filter time
Typ. 20 ms (load-dependent, on voltage dips for U
S
)
Status indicator
1 x green LED
1 x red LED
Protective circuit
Yes, within the scope of the operating voltage limits
Safe digital inputs IO0 to IO3 (if configured) and I4 to I11
Quantity
12 (4 of which are configurable as input or output)
Type
Digital
Input voltage range "0" signal
0 V DC … 5 V DC (for safe off)
Input voltage range "1" signal
11 V DC … 30 V DC
Typical current consumption at U
S
4 mA
Maximum total cable length
2000 m
Error detection time with 1-channel structure
< 1 s
Status indicator
12 x green LEDs
Safe digital outputs IO0 to IO3 (if configured)
Quantity
4 (if the configurable inputs/outputs are used as outputs)
Type
Digital
Nominal voltage
Permissible range
24 V DC (supply via A1/A2)
18 V DC … 30 V DC
(incl. all tolerances, incl. residual ripple)
WARNING: Loss of the safety function
The use of unsuitable voltage supplies and the incorrect connection of the voltage supply can result in the
loss of the safety function.
•
Only use power supply units with safe insulation and SELV/PELV in accordance with EN 50178 /
VDE 0160.
•
Connect the output-side GND connection of the power supply unit to the functional earth (FE) of the sys-
tem.