Technical data and ordering data
Leuze electronic
MSI 100/200
113
Limiting continuous current
50 mA
Protective circuit
Yes, within the scope of the operating voltage limits
Short circuit protected
Yes
Times
Reaction time
Max. 50 ms
See appendix "Switch-off time of the MSI 100/200 system" on page 124.
Recovery time
< 10 s
General specifications
Nominal operating mode
100% ED
Degree of protection in accordance with VDE 0470 part 1
Housing
Connection terminals
Installation location
IP20
IP20
Min. IP54
Mounting type
DIN rail mounting
Installation position
On horizontal DIN rail
Housing material
Unreinforced polyamide PA
Air and creepage distances between the circuits
Acc. to DIN EN 50178
Rated insulation voltage
250 V AC
Rated surge voltage / insulation
4 kV / basic insulation of the output contact current paths (13/14, 23/24, 33/34,
43/44) between one another
6 kV / safe insulation, reinforced insulation of the output contact current paths
(13/14, 23/24, 33/34, 43/44) from the other circuits
Degree of contamination
2
Overvoltage category
III
Maximum power loss at rated conditions
Ambient temperature of up to 40°C:
3932 mW
(with m = 4, n = 4, I
Load
= 4 A, I
Signal
= 50 mA)
Ambient temperature of up to 55°C (derating observed):
1532 mW
(with m = 4, n = 4, I
Load
= 1 A, I
Signal
= 50 mA)
See appendix "Calculation of the power loss" on page 120
Maximum number of safe extension modules with MSI 200
10
Maximum number of non-safe extension devices (gateways) in the
MSI 100/200 system
1
Maximum continuous current via MSI-TBUS
4 A
Signal outputs M0 to M3