For your safety
Leuze electronic
MSI 100/200
13
Disconnecting the USB
connection
For the safe operation of the machine or system, there must be no USB connection to the
safety modules.
For further information, refer to Chapter "USB interface" on page 28.
1.4.4
Safety when starting applications
Take the following into account when defining the start conditions for your machine or system:
–
The machine or system may only be started if it is ensured that no persons are located in
the danger zone.
–
Comply with the requirements of EN ISO 13849-1 with regard to the manual reset func-
tion.
This applies for:
–
The switching on of safe participants
–
The acknowledgment of device error messages
–
The canceling of start interlocks for safety functions
Observe start-up behavior
Some of the safe function blocks in the MSIsafesoft configuration software have parameters
for specifying a start interlock and/or a restart interlock.
For further information, refer to Chapter "System start-up and restart behavior" on page 19.
1.5
Directives and standards
The standards with which the MSI 100/200 system complies can be found in the certificate of
the approval body and the EC Declaration of Conformity.
You can find these documents on the Internet.