PROFINET interface – basic configuration
Leuze electronic
BPS 348i
70
8.6.19 Module 20 – Free resolution
8.6.20 Module 21 – distance to the bar code tape (BCB)
Module ID: 1020 or submodule ID: 1
The module is used to implement two parameters that facilitate free scaling of the output values
for position value and velocity value.
The free resolution is used if the adjustable resolutions that can be set in module 1 or module 10
are not suitable for the application. In modules 1 and 10, the
Resolution
parameter is set to value
Free resolution
. The measurement values are then converted for output with (multiplied by) the
parameter values stored in this module and output.
The module contains parameters (with parameter data length of 4 bytes), but no input data and
no output data.
Parameter
Rel.
Adr.
Data type Value range
De
-
fault
Measurement unit
Description
metr.
Inch
Position
0 … 1
unsign
16 bit
5 … 50.000
1000
mm
/1000
in
/100000
Free resolution of the position value:
Applies for all interfaces that selected the value
free
resolution
as resolution.
Velocity
2 … 3
unsign
16 bit
5 … 50.000
1000
(mm
/1000)
/s
(in
/100000)
/s
Free resolution of the velocity value
Applies for all interfaces that selected the value
free
resolution
as resolution.
Module ID: 1021 or submodule ID: 1
The module enables the transmission of the current distance between the BCB and read head
(in mm) to the PROFINET master.
This can be used to check the correct reading distance in the entire system.
Example: A fault in the position value determination is caused by an impermissible reading dis
-
tance at this location.
If value
255
is transmitted, a reading distance outside of the permissible reading field was calcu
-
lated.
If value
0
is transmitted, a valid distance could not be calculated.
The module contains input data (with input data length of 1 byte), but no parameters and no out
-
put data.
Input data
Rel.
Adr.
Data type Value range
Init-
Value
Measure
-
ment unit
Description
metr. Inch
Distance
0
unsign
8 bit
0 … 255
0
mm
in/10 Current distance between BCB and read head:
0: No distance calculated
255: Distance outside of the reading field