Online commands
Leuze electronic
BCL 608i
61
11.2 Online commands for system control
Activating sensor input
Deactivating sensor input
Acknowledgment
If no reference codes are defined, the device responds with the RS command
and corresponding status (see command RS). For valid codes, the output cor
-
responds to the following format:
RCyvxxzzzzzz
y, v, x and z are placeholders (variables) for the actual input.
y
Defined reference code no.
1
(code 1)
2
(code 2)
v
Storage location for reference code
0
RAM+EEPROM,
3
RAM only
xx
Defined code type (see command CA)
z
Defined code information (1 … 63 characters)
Command
RR
Command
+
Description
The command activates decoding. This command is used to activate the
reading gate. It remains active until it is deactivated by one of the following cri
-
teria:
• Deactivation by a manual command
• Deactivation by a switching input
• Deactivation upon reaching the specified read quality (equal scans)
• Deactivation by timeout
• Deactivation upon reaching a preset number of scans without informa
-
tion.
Parameter
No
Acknowledgment
None
Command
-
Description
The command deactivates decoding. This command can be used to deacti
-
vate the reading gate. Following deactivation, the read result is output.
Because the reading gate was manually deactivated and, thus, no GoodRead
criterion was met, a NoRead is output.
Parameter
No
Acknowledgment
None