PROFIBUS interface
Leuze electronic
AMS 304
i
86
TNT
35/7-2
4
V
9.4.3.18 Module 17: SSI interface
Description
The module defines the parameters for the SSI interface.
Attention!
The SSI interface can only represent positive distance values. If negative output values
are ascertained due to the offset or count direction, a zero value is output at the SSI
interface! In the event of a number overflow, all data bits are set to "1".
The
unit
,
offset
and
count direction
parameters of module 1 also apply to the SSI interface.
Notice!
If the SSI interface is not configured via module 17 (SSI interface) in PROFIBUS
operation, the SSI interface is deactivated.
If the SSI interface is operated without PROFIBUS (PROFIBUS OFF/SSI ON), configuration
is performed via the display.