Display and control panel AMS 304i
Leuze electronic
AMS 304
i
44
TNT
35/7-2
4
V
Additional important information on parameter handling can be found at the end of the
chapter.
PROFIBUS submenu
SSI submenu
Table 8.1:
Parameter handling submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard
Parameter
enabling
ON / OFF
The standard setting (
OFF
) prevents unintended parameter changes.
With parameter enabling activated (
ON
), the display is inverted. In this
state, it is possible to change parameters manually.
OFF
Password
Activate
password
ON / OFF
To enter a password, parameter enabling must be activated.
If a password is assigned, changes to the AMS 304
i
can only be made
after the password is entered.
The master password 2301 bridges the individually set password.
OFF
Password
entry
Configuration option of a four-digit numerical password.
Parameters to
default
By pressing the enter button
after selecting
Parameters to default
, all parameters are reset to their
standard settings without any further security prompts.
In this case, English is selected as the display language.
Table 8.2:
PROFIBUS submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard
Activation
ON / OFF
Activates or deactivates the AMS 304
i
as a PROFIBUS participant.
ON
Address
Value from 0 to 126
The PROFIBUS permits an address range from 0 to 126. Address 126 must
not be used for data communication. It may only be used temporarily for
commissioning.
The default address is 126.
The address must be assigned separately for each AMS 304
i
.
126
Table 8.3:
SSI submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard
Activation
ON / OFF
Activates or deactivates the AMS 304
i
as an SSI participant.
ON
Coding
Binary/gray
Specifies the output format of the measurement value.
Gray
Number of data
bits
24-bit/25-bit/26-bit
The measurement value can be displayed on the SSI interface in this data
width.
24 bit