PROFIBUS interface
Leuze electronic
AMS 304
i
52
TNT
35/7-2
4
V
9.3
PROFIBUS address entry
Notice!
Basic operation of the control panel/display is described in chapter 8.2. To set the address
parameter enabling must be activated. The display is inverted.
Attention!
The laser measurement system is deactivated on the PROFIBUS when parameter enabling
is activated via the display. The device is reactivated on the PROFIBUS after parameter
enabling is exited.
9.3.1
Entering the PROFIBUS addresses via the display
To do this proceed as follows:
ª
Activate parameter enabling.
ª
Select the PROFIBUS submenu.
ª
Select the address menu item [ ].
ª
Enter the PROFIBUS address of the laser measurement system; set to a value between
1 and 126 (default: 126).
ª
Deactivate parameter enabling.
9.4
PROFIBUS GSD file
9.4.1
General information on the GSD file
If the AMS 304
i
is operated in a PROFIBUS network, configuration must be performed
exclusively via the PROFIBUS. The functionality of the laser measurement system is defined
via modules. The parameters and their functions are structured in the GSD file using module.
A user-specific configuration tool is used during PLC program creation to integrate the
required modules and configure them appropriately for the measurement application.
During operation of the laser measurement system on the PROFIBUS all parameters are set
to default values. If these parameters are not changed by the user, the device functions using
the default settings supplied by Leuze electronic. For the default settings of the device
please refer to the following module descriptions.
Notice!
At least one module in the GSD file must be activated in the configuration tool for the control,
usually the
Position value module
.