Technical data
Standards and operating conditions
Conformities/approvals
Conformity
CE
2014/35/EU
Low-Voltage Directive
2014/30/EU
EMC Directive (reference: CE-typical drive system)
EAC
TR TC 004/2011
Eurasian conformity: safety of low voltage equipment
TP TC 020/2011
Eurasian conformity: electromagnetic compatibility of tech-
nical means
Approval
CCC
GB Standard 12350-2009
cULus
UL 61800-5-1
for USA and Canada (requirements of the CSA 22.2 No. 14)
Industrial Control Equipment, Lenze File No. E132659
Protection of persons and device protection
Enclosure
IP55
EN 60529
Type 4 indoor only
Type 12
NEMA 250
Insulation resistance
Overvoltage category III
EN 61800-5-1
Site altitude 0 … 2000 m above sea level
Overvoltage category II
EN 61800-5-1
Site altitude more than 2000 m above sea level:
External measures for compliance with overvoltage cate-
gory II are necessary, e.g. connection of an isolating trans-
former upstream , connection of an overvoltage protection
device upstream
Protective insulation of control circuits
Safe separation from the mains supply by
means of double/increased insulation for
digital inputs and outputs
EN 61800-5-1
Site altitude 0 … 2000 m above sea level
Upstream connection of overvoltage pro-
tection device
EN 61800-5-1
Site altitude more than 2000 m above sea level:
Additional external separating measures necessary for pur-
poses of safe separation.
Protective measures against
Short circuit
EN 61800−5−1
To a limited extent, fault acknowledgement necessary
earth fault
EN 61800−5−1
To a limited extent, fault acknowledgement necessary
Overvoltage
Yes
Motor stalling
Yes
Motor overtemperature
I
2
xt-monitoring
Leakage current
> 3.5 mA AC, > 10 mA DC
EN 61800-5-1
Observe regulations and safety instructions!
Equipotential bonding
Additional M5 thread with terminal at the terminal box for
connecting another PE cable (up to max. 6 mm
2
)
Total fault current
Residual current operated switch 30 mA,
Type B
In TN power supply systems
Cyclic mains switching
3 times a minute, max. 20 times per hour
Mains switching 3 times in one minute must be followed by
a pause of 9 minutes.
Starting current
5.6 A mains power-on current
Technical data
Standards and operating conditions
Conformities/approvals
78