29
EDBSV571 EN 1.0
EN
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default
Selection
P232
Preset PID Setpoint
#2
0.0
P204
P205
TB-13B activated; P122 = 3 and P200 = 1 or 2
P233
Preset PID Setpoint
#3
0.0
P204
P205
TB-13C activated; P123 = 3 and P200 = 1 or 2
P234
(2)
Preset PID Setpoint
#4
0.0
P204
P205
TB-13D activated; P124 = 3 and P200 = 1 or 2
P240
Sleep Threshold
0.0
0.0 {Hz} 500.0
•
If drive speed < P240 for longer than
P241, output frequency = 0.0 Hz; drive
display = SLP
•
P240 = 0.0: Sleep mode is disabled.
•
P200 = 0…2: Drive will start again when
speed command is above P240
•
P242 > 0.0: Drive will restart when the PID
feedback differs from the setpoint by more
than the value of P242
or
when the PID
loop requires a speed above P240.
P241
Sleep Delay
30.0
0.0 {s} 300.0
P242
Sleep Bandwidth
0.0
0.0 B
max
Where: B
max
= |(P205 - P204)|
P243
Feedback Sleep
Entry Threshold
0.0
P204
P205
Active only when P244 = 1 or 2
P244
Sleep Entry Mode
0
0 Enter SLEEP if Drive Speed <P240
For time longer than P241
1 Enter SLEEP if Feedback >P243
For time longer than P241 or same as Sel 0
2 Enter SLEEP if Feedback <P243
For time longer than P241 or same as Sel 0
P245
Sleep Entry Stop
Type
0
0 Coast to Stop
1 Ramp to Stop
2 Stop with P111 settings
P246
Feedback Recovery
from Sleep
Threshold
0.0
P204
P205
Active only when P247 = 1 or 2
P247
Sleep Recovery
Mode
0
0 Recovery if Speed Setpoint > P240
or if PID feedback differs from
setpoint by more than P242
1 Recovery only if Feedback < P246
2 Recovery only if Feedback > P246
P250
Auto Rinse in Sleep
Mode
0
0 Disabled
Activated in sleep mode only.
Sleep Recovery cancels Auto Rinse
1 Enabled
P251
Time Delay
between Auto
Rinses
30.0
0.0 {min} 6553.5
Time delay reset by re/entering sleep mode
P252
Auto Rinse Speed
0.0
-500.0 {Hz} 500.0
If P112 = 1, negative sign = reverse direction
P253
Auto Rinse Time
0.0
0.0 {sec} 6553.5
Does not include time to decel back to speed
Auto Pump Rinse Setup:
P250=1 (Enabled)
P251=# minutes between each Pump
Rinse
P252=Hz speed of Pump Rinse
P253=# seconds Pump Rinse duration
Output
Fr
equency
Time
P252
P104/
P125
P105/
P126
P253
P251
Pump Rinse Speed
Pump Rinse Time
Delay Time
between each
Pump Rinse
P280
Current Level:
Flying Restart
Type 2
70.0
0.0 {%} P171
Maximum current during Type 2 flying restart
operation
P281
Decel Time: Flying
Restart Type 2
3.0
0.0 {sec} 3600.0
Deceleration rate used during Type 2 flying
restart operation