24
EDBSV571 EN 1.0
EN
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default
Selection
p131
Preset Speed #1
0.0
0.0 {Hz} 500
•
Speed setting is used by P158
p132
Preset Speed #2
0.0
0.0 {Hz} 500
p133
Preset Speed #3
0.0
0.0 {Hz} 500
p134
Preset Speed #4
0.0
0.0 {Hz} 500
p135
Preset Speed #5
0.0
0.0 {Hz} 500
p136
Preset Speed #6
0.0
0.0 {Hz} 500
p137
Preset Speed #7
0.0
0.0 {Hz} 500
p138
Preset Speed #8
0.0
0.0 {Hz} 500
p145
Loss of Load
Threshold
0
0 {%} 200
P140, P142 = 10: Output will energize if
motor load falls below the P145 value longer
than the P146 time
p146
Loss of Load Delay
0.0
0.0 {s} 240.0
p149
Analog Output
Offset
0.0
0 {%} 100
Scaled value. Example: P149 = 10%, Scaled
variable = freq, P150 = 1, P152 = 60Hz; then
TB30 = 0VDC below 6Hz
p150
TB-30 Output
9
0 None
2-10 VDC signal can be converted to 4-20 mA
with a total circuit impedance of 500
W
1 0-10 VDC Output Frequency
2 2-10 VDC Output Frequency
3 0-10 VDC Load
4 2-10 VDC Load
5 0-10 VDC Torque
6 2-10 VDC Torque
7 0-10 VDC Power (kW)
8 2-10 VDC Power (kW)
9 Network Controlled
SMV models < 15HP (11kW) require an
optional communication module (refer to the
network module documentation).
10 Sequencer Controlled
Value set in individual sequencer segments
p152
TB-30 Scaling:
Frequency
60.0
3.0 {Hz} 2000
If P150 = 1 or 2, sets the frequency at which
output equals 10 VDC
p153
TB-30 Scaling: Load
200
10 {%} 500
If P150 = 3 or 4, sets the Load (as a percent of
drive current rating) at which output equals
10 VDC.
p154
TB-30 Scaling:
Torque
100
10 {%} 1000
If P150 = 5 or 6, sets the Torque (as a percent
of motor rated torque) at which output
equals 10 VDC
p155
TB-30 Scaling:
Power (kW)
1.0
0.1 {kW} 200.0
If P150 = 7 or 8, sets the power at which
output equals 10 VDC