10
EDBSV571 EN 1.0
EN
Technical Data
600VAC Models
600V Three Phase (3/PE) (425...660V); 48...62Hz
Type
Power
Mains Current
Output Current
Heat Loss (Watts)
Hp
kW
A
Cont (I
n
)
A
Max I
%
N1/IP31
ESV751--6T--
1
0.75
2
1.7
200
37
ESV152--6T--
2
1.5
3.2
2.7
200
51
ESV222--6T--
3
2.2
4.4
3.9
200
68
ESV402--6T--
5
4
6.8
6.1
200
101
ESV552--6T--
7.5
5.5
10.2
9
200
148
ESV752--6T--
10
7.5
12.4
11
200
172
NOTES:
Output Current: The Output Current Maximum (%) is a percentage of the Output Current Continuous
Amps (In) rating and is adjustable in parameter P171.
STOP!
•
For installations above 1000m a.m.s.l., derate I
n
by 5% per 1000m, do
not exceed 4000m a.m.s.l.
•
Operation above 40°C, derate I
n
by 2.5% per °C, do not exceed 55°C.
Output Current (In) derating for Carrier Frequency (P166) for NEMA 1
(IP31) Models:
- If P166=2 (8 kHz), derate I
n
to 92% of drive rating
- If P166=3 (10 kHz), derate I
n
to 84% of drive rating
Output Current (In) derating for Carrier Frequency (P166) for NEMA 4X
(IP65) Models:
- If P166=1 (6 kHz), derate I
n
to 92% of drive rating
- If P166=2 (8 kHz), derate I
n
to 84% of drive rating
- If P166=3 (10 kHz), derate I
n
to 76% of drive rating