28
EDBSV571 EN 1.0
EN
Commissioning
4.5.4
PID Parameters
Code
Possible Settings
IMPORTANT
No.
Name
Default
Selection
P200
PID Mode
0
0 Disabled
•
Normal-acting: As feedback increases,
motor speed decreases
•
Reverse-acting: As feedback increases,
motor speed increases
•
PID mode is disabled in Vector Torque mode
(P300 = 5)
•
Selections 3, 4: If P112=1, PID controller
output sets the speed, (range -max freq
to +max freq)
1 Normal-acting
2 Reverse-acting
3 Normal-acting, Bi-directional
4 Reverse-acting, Bi-directional
NOTE
To activate PID mode, one of the TB-13 inputs (P121...P124) must be used to select
the Auto Reference that matches the desired PID setpoint reference. If the selected
PID setpoint reference uses the same analog signal as the PID feedback (P201), an
F.IL
fault will occur.
Example:
The desired PID setpoint reference is the keypad (
p
and
q
). Set TB-13x = 6
(Auto Reference: Keypad):
•
TB-13x = closed: PID mode is active
•
TB-13x = open: PID mode is disabled and the drive speed will be controlled by the
reference selected in P101.
p201
PID Feedback
Source
0
0 4-20 mA (TB-25)
Must be set to match the PID feedback signal
1 0-10 VDC (TB-5)
2 Drive Load (P507)
3 Feedback from Network
p202
PID Decimal Point
1
0 PID Display = XXXX
Applies to P204, P205, P214, P215, P231...
P233, P242, P522, P523
1 PID Display = XXX.X
2 PID Display = XX.XX
3 PID Display = X.XXX
4 PID Display = .XXXX
p203
(2)
PID Units
0
0 %
Select the UNITS LED that will be illuminated
when the drive is running in PID control mode
1 /UNITS
2 AMPS
3 NONE
p204
Feedback at
Minimum Signal
0.0
-99.9
3100.0
Set to match the range of the feedback signal
being used
Example:
Feedback signal is 0 - 300 PSI; P204
= 0.0, P205 = 300.0
p205
Feedback at
Maximum Signal
100.0
-99.9
3100.0
p207
Proportional Gain
5.0
0.0 {%} 1000.0
Used to tune the PID loop:
•
Increase P207 until system becomes
unstable, then decrease P207 by 10-15%
•
Next, increase P208 until feedback matches
setpoint
•
If required, increase P209 to compensate for
sudden changes in feedback
p208
Integral Gain
0.0
0.0 {s} 20.0
p209
Derivative Gain
0.0
0.0 {s} 20.0
NOTE
• Derivative Gain is very sensitive to noise on the feedback signal. Use with care.
• Derivative Gain is not normally required in pump and fan applications
p210
PID Setpoint Ramp
20.0
0.0 {s} 100.0
•
time of setpoint change from P204 to P205
or vice versa.
•
Used to smooth the transition from one PID
setpoint to another, such as when using the
Preset PID Setpoints (P231...P233)
p214
Minimum Alarm
0.0
P204
P205
Use with P140, P142 = 18...23
P215
Maximum Alarm
0.0
P204
P205
P231
Preset PID Setpoint
#1
0.0
P204
P205
TB-13A activated; P121 = 3 and P200 = 1 or 2