21
EDBSV571 EN 1.0
EN
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
p107
(1)
Line Voltage
Selection
1*
0 Low (120, 200, 400, 480VAC)
* The default setting is 1 for all drives except
when using “Reset to 50Hz default settings”
(Parameter P199, selection 4) with 480V
models. In this case, the default setting is 0.
1 High (120, 240, 480, 600VAC)
p108
Motor Overload
100
30 {%} 100
P108 = motor current rating x 100
SMV output rating
Example: if motor = 3amps and SMV =
4amps, then P108 = 75%
NOTE
Do not set above rated motor current as listed on the motor dataplate. The motor
thermal overload function of the SMV is UL approved as a motor protection device.
Cycling power after an overload fault could result in significantly reducing the motor
life.
P109
Motor Overload
Type
0
0 Speed Compensation
Reduces the allowable continuous
current when operating below 30Hz.
Ir
100%
60%
30 f
1
0
V0108
Ir: rated current (%), f: motor frequency (Hz)
1 No Speed Compensation
Example: Motor is cooled by forced
ventilation as apposed to shaft
mounted, self cooling fans.