Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default
Selection
p176
Keypad Setpoint
Single Press
Increment
0.1
0.1
100.0
Used for run screen setpoint editing only.
If P176 >0.1 then scrolling of keypad setpoint
is enabled.
p178
Display Frequency
Multiplier
0.00
0.00
650.00
•
Allows frequency display to be scaled
•
P178 = 0.00: Scaling disabled
•
P178 > 0.00: Display = Actual Frequency
X P178
EXAMPLE
If
P178 = 29.17 and actual frequency = 60 Hz, then Drive displays 1750 (rpm)
p179
Run Screen Display
0
0 {Parameter Number}
599
•
0 = Normal Run Screen, this display depends
on mode of operation. Refer to section 4.2.
•
Other selections choose a diagnostic
parameter to display (P501…P599).
•
Parameters P560 - P564 are selectable
if the sequencer is enabled (P700 is not
0). P560-P564 are not visible until P700
is enabled.
p180
Oscillation
Damping Control
0
0 80
0 = Damping disabled
Compensation for resonances within drive
p181
Skip frequency 1
0.0
0.0
{Hz}
500
•
Drive will not run in the defined skip range;
used to skip over frequencies that cause
mechanical vibration
•
P181 and P182 define the start of the
skip ranges
•
P184 > 0 defines the bandwidth of both
ranges.
p182
Skip frequency 2
0.0
0.0
{Hz}
500
p184
Skip frequency
bandwidth
0.0
0.0
{Hz}
10.0
NOTE
Bandwidth (Hz) = f
s
(Hz) + P184 (Hz) f
s
= P181 or P182
EXAMPLE:
P181 = 18 Hz and P184 = 4 Hz; skip range is from 18 to 22 Hz
p185
Voltage Midpoint
V/Hz characteristic
0
0.0
{V}
P165
Valid only when P300 = 0 or 2.
Use with P187 to define midpoint on V/Hz
curve.
p187
(2)
Frequency
Midpoint V/Hz
characteristic
0.0
0.0
{Hz}
P167
Valid only when P300 = 0 or 2.
Use with P185 to define midpoint on V/Hz
curve.
p190
Motor Braking
0 Disabled
Flux brake OFF.
1 Braking with BUS threshold
When drive is in deceleration and V
bus
>
V
deceleration freeze
(114% of the rated V
bus
), the flux
brake will be turned ON.
2 Braking always on with
deceleration
As long as drive is in deceleration, the flux
brake will be ON.
3 Braking with bus regulator
When drive is in deceleration and V
bus
> V
deceleration
freeze
(114% of the rated V
bus
), the motor speed will be
increased to reduce the bus voltage. Determined by
the value in P191, the speed increment = slip speed *
P191(%) / 37.
4 Special
(Consult factory before using)
WARNING
Flux braking can cause heat in the motor. To avoid damage to the motor, use a PTC
to protect the motor. If the flux brake is used too frequently, the drive will trip fault
“F_PF”.
p191
Motor Brake Level
0
0
{%}
75
(flux
braking
disabled)
Active when P190 > 0 and drive is in deceleration
mode. Use to reduce deceleration time on high
inertia loads.
NOTE:
Over usage of P190 can cause frequent
‘overload’ trips “F.PF”
Not active for P300 = 5 (Torque mode)