Troubleshooting and fault elimination
821XKlimaBA0399
8-3
Display
Remedy
Cause
Fault
H05
Internal fault
Contact Lenze
LU
Undervoltage
DC-bus voltage too low
-
Check mains voltage
-
Check supply module
OC1
Short circuit
Short circuit
Find out cause of short circuit; check
cable
Excessive capacitive charging
current of the motor cable
Use motor cable which is shorter or of
lower capacitance
OC2
Earth fault
Grounded motor phase
Check motor; check cable
OC2
Earth fault
Excessive capacitive charging
current of the motor cable
Use motor cable which is shorter or of
lower capacitance
OC3
Overload inverter
during acceleration or
short circuit
Acceleration time too short (C012)
-
Increase acceleration time
-
Check drive selection
during acceleration or
short circuit
Defective motor cable
Check wiring
Interturn fault in the motor
Check motor
OC4
Overload controller
during deceleration
Deceleration time too short (C013)
-
Increase deceleration time
-
Check the selection of the brake
resistor or connect the brake chopper
OC5
I x t overload
Frequent and too long acceleration
processes with overcurrent
Check drive dimensioning
OC6
Overload motor
Motor is thermally overloaded, for
instance, because of
-
impermissible continuous
current
-
Check drive selection
-
frequent or too long acceleration
processes
-
Check the setting under C120
OH
Heat sink temperature
is higher than the value
set in the controller
Ambient temperature
T
u
> + 40
C or + 50
C
-
Allow controller to cool and ensure
ventilation
-
Check the ambient temperature in the
control cabinet
Heat sink very dirty
Clean heat sink
Incorrect mounting position
Change mounting position
OH3
PTC monitoring
Motor too hot because of
excessive current or frequent and
too long acceleration
Check drive dimensioning
PTC not connected
Connect PTC or switch-off monitoring
(C0585= 3)
OH4
Overtemperature unit
Inside unit too hot
-
Reduce controller load
-
Improve cooling
-
Check fan in the controller
OU
Overvoltage
Mains voltage too high
Check voltage supply
OU
Overvoltage
Feedback operation
Braking operation
-
Increase deceleration times.
-
For operation with brake choppers:
- Check the selection and connection
of the brake resistor
- Increase the deceleration times
Earth leakage on the motor side
Check motor cable and motor for earth
fault (disconnect motor from inverter)
Show/Hide Bookmarks
Содержание 8210 HVAC Series
Страница 52: ...Commissioning 5 14 821XKlimaBA0399 Show Hide Bookmarks...
Страница 62: ...Commissioning 5 24 821XKlimaBA0399 Show Hide Bookmarks...
Страница 64: ...During operation 6 2 821XKlimaBA0399 Show Hide Bookmarks...
Страница 78: ...Configuration 7 14 821XKlimaBA0399 Show Hide Bookmarks...
Страница 84: ...Troubleshooting and fault elimination 8 6 821XKlimaBA0399 Show Hide Bookmarks...
Страница 88: ...Accessories 9 4 821XKlimaBA0399 Show Hide Bookmarks...
Страница 92: ...Index 10 4 821XKlimaBA0399 Show Hide Bookmarks...
Страница 93: ...Index 821XKlimaBA0399 10 5 Show Hide Bookmarks...
Страница 94: ...Index 10 6 821XKlimaBA0399 Show Hide Bookmarks...