Commissioning
821XKlimaBA0399
5-13
5.5.1
Standardisation of a process value
Setting range 821X/822X /824X:
Code
Name
Possible settings
IMPORTANT
Code
Name
Lenze Selection
Info
IMPORTANT
C500* Display factor
process value
numerator
2000
1
{1}
25000
C501* Display factor
process value
denominator
10
1
{1}
25000
Function
Adaption of the field-frequency related parameters C010, C011, C017, C019, C037,
C038, C039, C046, C049, C050, C051 and C181 to an application datum to be
controlled, e.g. speed. The codes display the absolute value of an application datum.
Adjustment
The display value CXXX is calculated from:
CXXX
C011
200
ô
C500
C501
Example
Relative and absolute selection and display of a speed setpoint.
Values: Pset = 5 bar, f
dmax
= 50 Hz (= C011)
a) Relative standardisation in %
100, 00(%)
50
200
ô
4000
10
e.g. C500 = 4000, C501 = 10
b) Absolute standardisation in physical units
5 (bar)
50
200
ô
200
10
e. g. C500 = 200, C501 = 10
Show/Hide Bookmarks
Содержание 8210 HVAC Series
Страница 52: ...Commissioning 5 14 821XKlimaBA0399 Show Hide Bookmarks...
Страница 62: ...Commissioning 5 24 821XKlimaBA0399 Show Hide Bookmarks...
Страница 64: ...During operation 6 2 821XKlimaBA0399 Show Hide Bookmarks...
Страница 78: ...Configuration 7 14 821XKlimaBA0399 Show Hide Bookmarks...
Страница 84: ...Troubleshooting and fault elimination 8 6 821XKlimaBA0399 Show Hide Bookmarks...
Страница 88: ...Accessories 9 4 821XKlimaBA0399 Show Hide Bookmarks...
Страница 92: ...Index 10 4 821XKlimaBA0399 Show Hide Bookmarks...
Страница 93: ...Index 821XKlimaBA0399 10 5 Show Hide Bookmarks...
Страница 94: ...Index 10 6 821XKlimaBA0399 Show Hide Bookmarks...