Troubleshooting and fault elimination
821XKlimaBA0399
8-1
8 Troubleshooting and fault elimination
You can recognize immediately whether a fault has occured by
display elements or status information (chapter 8.1).
The faults can be analysed by using the history buffer (chapter 8.2)
and the list in chapter 8.3. This list helps you to eliminate the faults.
8.1 Troubleshooting
8.1.1
Display at the controller
During operation without operating module two LED at the unit
front indicate the operating status.
LED
Operating status
green
red
Operating status
on
off
Controller enabled
on
on
Mains switched on, automatic start inhibited (AS_LC)
blinking
off
Controller inhibited
off
blinking every second
Fault message, check under C161
off
blinking every 0.4 seconds
Undervoltage switch-off
off
off
Programming mode
8.1.2
Display at the operating module
Status indications in the display indicate the controller status.
Display
Meaning
OV
Overvoltage
UV
Undervoltage
IMAX
Set current limit exceeded
TEMP
Heat sink temperature near switch-off
Show/Hide Bookmarks
Содержание 8210 HVAC Series
Страница 52: ...Commissioning 5 14 821XKlimaBA0399 Show Hide Bookmarks...
Страница 62: ...Commissioning 5 24 821XKlimaBA0399 Show Hide Bookmarks...
Страница 64: ...During operation 6 2 821XKlimaBA0399 Show Hide Bookmarks...
Страница 78: ...Configuration 7 14 821XKlimaBA0399 Show Hide Bookmarks...
Страница 84: ...Troubleshooting and fault elimination 8 6 821XKlimaBA0399 Show Hide Bookmarks...
Страница 88: ...Accessories 9 4 821XKlimaBA0399 Show Hide Bookmarks...
Страница 92: ...Index 10 4 821XKlimaBA0399 Show Hide Bookmarks...
Страница 93: ...Index 821XKlimaBA0399 10 5 Show Hide Bookmarks...
Страница 94: ...Index 10 6 821XKlimaBA0399 Show Hide Bookmarks...