Troubleshooting and fault elimination
821XKlimaBA0399
8-5
8.4 Reset of fault indications
TRIP
After eliminating the fault, the pulse inhibit will only be reset after the
acknowledgement of TRIP.
Note!
If the TRIP source is still active, the TRIP cannot be reset.
Code
Name
Possible settings
IMPORTANT
Code
Name
Lenze Selection
Info
IMPORTANT
C170
¤
TRIP-reset
selection
-0-
TRIP-reset by pressing the STP
key or a LOW signal at ctrl.
enable
-1-
Auto-TRIP reset
C171 Delay for
Auto-TRIP-Reset
0,00
0,00
{0.01s}
60,00
Function
You can select whether the fault is to be reset automatically or manually.
Activation
C170 = -0-:
-
Manual TRIP-reset
-
STP key
-
LOW signal at terminal 28
C170 = -1-:
Auto-TRIP reset resets all faults after the time set under C171.
Important
-
Mains switching always resets TRIP.
-
With more than 8 Auto-TRIP resets within 10 minutes, the controller sets TRIP and
indicates rST.
Show/Hide Bookmarks
Содержание 8210 HVAC Series
Страница 52: ...Commissioning 5 14 821XKlimaBA0399 Show Hide Bookmarks...
Страница 62: ...Commissioning 5 24 821XKlimaBA0399 Show Hide Bookmarks...
Страница 64: ...During operation 6 2 821XKlimaBA0399 Show Hide Bookmarks...
Страница 78: ...Configuration 7 14 821XKlimaBA0399 Show Hide Bookmarks...
Страница 84: ...Troubleshooting and fault elimination 8 6 821XKlimaBA0399 Show Hide Bookmarks...
Страница 88: ...Accessories 9 4 821XKlimaBA0399 Show Hide Bookmarks...
Страница 92: ...Index 10 4 821XKlimaBA0399 Show Hide Bookmarks...
Страница 93: ...Index 821XKlimaBA0399 10 5 Show Hide Bookmarks...
Страница 94: ...Index 10 6 821XKlimaBA0399 Show Hide Bookmarks...