23 RG-MHMOD
Drive Control & Communication
AC Tech
Register
Number
(hexadecimal
representation)
Parameter
1
Parameter Name
Range of Adjustment
Modbus value (decimal value)
Factory Default
95 (5F)
44
TB10B OUT
00 - None
01 - 0 - 10 VDC
02 - 2 - 10 VDC
00 - None
96 (60)
45
@TB10B
10 - 200 (10 - 200%)
125 (125%)
98 (62)
47
TB13A
00 - None
01 - 0 - 10 VDC
02 - 4 - 20 mA
03 - PRESET #1
04 - DEC FREQ
05 - REVERSE
00 - None
99 (63)
48
TB13B
00 - None
01 - 0 - 10 VDC
02 - 4 - 20 mA
03 - PRESET #2
04 - INC FREQ
00 - None
100 (64)
49
TB13C
00 - None
01 - 0 - 10 VDC
02 - 4 - 20 mA
03 - PRESET #3
04 - HAND
05 - REVERSE
00 - None
101 (65)
50
TB13D
00 - EXT Fault
01 - EXT /Fault
02 - EXT Clear
00 - EXT Fault
103 (67)
104 (68)
105 (69)
52
53
54
TB14OUT
TB15OUT
RELAY
00 - None
01 - Run
02 - Fault
03 - INV Fault
04 - Fault Lockout
05 - @ Speed
06 - Above Preset #3
07 - Current Limit
08 - AUTO/HAND SRC
09 - FLWR PRESET
10 - MIN/MAX ALARM
11 - INV MIN/MAX ALM
12 - MIN ALARM
13 - INV MIN ALARM
14 - MAX ALARM
15 - INV MAX ALARM
16 - RUN REVERSE
00 - None
106 (6A)
55
TB5B LOSS
00 - Fault
01 - Preset #3
00 - Fault
108 (6C)
57
SERIAL
00 - Disable
01 - w/ Timer
02 - w/o Timer
00 - Disable
109 (6D)
58
ADDRESS
1 - 247
30
112 (70)
61
PASSWORD
0000 - 9999
0019
114 (72)
63
SOFTWARE
(View Only)
(N/A)
1
= Drive's programming parameter number;
2