RG-MHMOD 14
Drive Control & Communication
5.3 Drive Size - Register #21
Table 9 lists the MCH Series drives. Register 21 will contain the value in the "Size" column. The drives are
listed in ascending order by the "Size" number.
Table 9: Drive Size - Register #21
Size
HP
Voltage
Size
HP
Voltage
Size
HP
Voltage
Size
HP
Voltage
00
0.25
120
13
50
480
27
1
590
42
100
590
01
0.25
240
14
60
480
28
1.5
590
43
125
590
02
0.5
240
15
1
480
29
2
590
44
150
590
03
1
240
16
1.5
480
30
3
590
45
200
590
04
1.5
240
17
2
480
31
5
590
46
75
480
05
2
240
18
3
480
32
7.5
590
47
100
480
06
3
240
19
5
480
33
10
590
48
125
480
07
5
240
20
7.5
480
34
15
590
49
150
480
08
7.5
240
21
10
480
35
20
590
50
200
480
09
10
240
22
15
480
36
25
590
51
30
240
10
15
240
23
20
480
37
30
590
52
40
240
11
20
240
24
25
480
38
40
590
53
50
240
12
25
240
25
30
480
39
50
590
54
60
240
26
40
480
40
60
590
55
75
240
41
75
590
56
100
240
5.4 Drive Status - Registers #24-29
When reading parameter #24, the number of words requested must be 6. This is an exception to the rule of
being able to read only one register at a time. The drive will send back 6 registers to the master. If 6 words
are requested at parameter #24, the following will be returned:
Table 10: 6 Register read at #24
Parameter
Data Byte
Command Speed
D1H D1L
Actual Speed
D2H D2L
Load
D3H
Operation Status
D3L
Rotational Direction
D4H
Control Mode
D4L
Speed Command Source
D5H
Auto/Hand Status
D5L
Present Fault
D6H
Command Rotation
D6L