© Copyright Lenovo 2015
Chapter 3: Installing G7052 Hardware and Options
45
5. Secure the switch to the front rack posts with M6 screws (Item 3), washers
(Item 5), and clip nuts (Item 4). Torque the screws to approximately 5.7 Nm +/-
0.1 Nm (50 inch-pounds).
6. Attach the rear alignment plate (Item 7) to the rear rack posts with M6 screws
(Item 3), washers (Item 5), and clip nuts (Item 4). Torque the screws to
approximately 5.7 Nm +/- 0.1 Nm (50 inch-pounds).
7. If installing the 1U air-duct option, see the instruction on
8. Connect all external cables in accordance with the
5
3
4
7
3
5